Gaseous Fire Suppression System

FM-200 (HFC227ea)
Fire Suppression System

Category: Gaseous Fire Suppression System

FM-200 (HFC227ea) Fire Suppression System — Fast-Acting Clean Agent Protection for Indonesia’s Critical Facilities

PT Totalfire Indonesia designs and installs FM-200 (HFC227ea) fire suppression systems — the world’s most widely deployed clean agent suppression technology — for server rooms, data centers, control rooms, UPS rooms, electrical switchgear, telecommunications facilities, and other mission-critical environments across Indonesia.

FM-200 suppresses fire in 10 seconds or less, leaves zero residue, and is safe for occupied spaces at design concentrations — making it the benchmark clean agent solution for any facility where fire damage, system downtime, or secondary water damage cannot be tolerated. More than 100,000 FM-200 systems have been installed across over 70 countries, making it the most proven clean agent fire suppression technology in the world.

All our FM-200 system designs comply with NFPA 2001 (Standard on Clean Agent Fire Extinguishing Systems) and ISO 14520, backed by our ISO 9001:2015 and ISO 45001:2018 certifications.

What Is FM-200 (HFC227ea)?

FM-200 is the trade name for heptafluoropropane (HFC-227ea), a colorless, odorless, electrically non-conductive clean agent stored as a liquefied gas under nitrogen pressure. When a fire is detected, FM-200 discharges as a vapor that floods the protected enclosure within seconds, extinguishing the fire through a dual mechanism before it can cause significant damage.

FM-200 belongs to the HFC (hydrofluorocarbon) family of clean agents. It was developed as a replacement for halon — the highly effective but ozone-depleting suppression agent phased out under the Montreal Protocol. FM-200 has zero ozone depletion potential (ODP) and is fully compliant with Indonesian environmental regulations, including Keputusan Menteri Perindustrian No. 33 Tahun 2007 regarding global warming substances.

FM-200 is classified as a clean agent per the NFPA 2001 definition: electrically non-conductive, volatile, and gaseous — leaving no residue upon evaporation. This means no cleanup, no equipment contamination, and no secondary damage beyond the fire itself.

How FM-200 Extinguishes Fire

FM-200 suppresses fire through two simultaneous mechanisms that work together to collapse the fire triangle faster than any single-mechanism agent:

1. Heat Absorption (Thermodynamic Mechanism)

FM-200 absorbs large amounts of heat energy from the combustion reaction as it vaporizes in the protected space. By rapidly removing heat — one of the three elements of the fire triangle — FM-200 reduces the fire’s energy below the threshold required for self-sustaining combustion. This is the primary suppression mechanism and accounts for the majority of FM-200’s fire-extinguishing effectiveness.

2. Chemical Interference (Catalytic Mechanism)

FM-200 also interferes with the chemical chain reactions that sustain combustion at the molecular level. The HFC-227ea molecule reacts with free radicals produced by the combustion process, interrupting the chain reaction and accelerating suppression. This chemical action means FM-200 achieves effective suppression at lower concentrations than purely oxygen-depleting agents — allowing the system to work without reducing oxygen to levels unsafe for human presence.

The combination of these two mechanisms allows FM-200 to achieve fire suppression at a design concentration of approximately 7–8% by volume — reached within 10 seconds of discharge initiation — while maintaining an oxygen concentration well above the safe human threshold.

Why FM-200 Is the Standard Choice for Server Rooms & Data Centers in Indonesia

Suppresses Fire in 10 Seconds or Less

FM-200 reaches its design concentration throughout the protected enclosure in 10 seconds or less from the moment of discharge — before a fire can grow large enough to cause significant damage to servers, storage systems, networking equipment, or power infrastructure. For live IT environments where even a small fire can cause catastrophic data loss or hardware destruction, this speed is the critical performance criterion that makes FM-200 the preferred choice.

Zero Residue — Servers Stay Clean

FM-200 vaporizes completely upon discharge, leaving absolutely no residue on any surface. Unlike water-based systems (which flood and short-circuit equipment), dry powder systems (which leave fine contaminating powder throughout the space), or foam systems (which coat every surface), FM-200 discharge leaves the protected room in exactly the same condition as before — except that the fire is out. Equipment can be inspected and returned to service after system ventilation, without decontamination.

Electrically Non-Conductive

FM-200 does not conduct electricity. It can be safely discharged into a room full of live, energized electrical equipment — servers running at full load, powered UPS systems, active switchgear — without any risk of electrical short circuit from the agent itself. This is a mandatory requirement for data center and server room protection.

Safe for Occupied Spaces at Design Concentration

FM-200 at its design concentration of 7–8% by volume is safe for human occupancy per NFPA 2001 NOAEL (No Observed Adverse Effect Level) limits. Unlike CO2 systems — which discharge at immediately life-threatening concentrations — an FM-200 discharge will not instantly incapacitate or kill building occupants who have not yet evacuated. This does not eliminate the requirement for pre-discharge alarms and evacuation, but it provides a critical safety margin in facilities where rapid complete evacuation cannot always be guaranteed.

Compact Storage — Minimal Equipment Room Space

FM-200 is stored as a liquefied gas under nitrogen pressure in compact cylinders. For a typical 50 m² server room, the entire FM-200 cylinder bank may be stored in as little as 0.5–1 m² of floor space — either inside the protected room itself or in an adjacent equipment area. This compact footprint is a significant practical advantage in data centers and telecommunications rooms where every square meter of space has high value.

Globally Proven — Over 100,000 Installations Worldwide

FM-200 has been installed in more than 100,000 systems across more than 70 countries since its introduction. This track record provides a level of real-world validation — in the widest range of facility types, climates, and operating conditions — that no other clean agent can match. PT Totalfire Indonesia has extensive experience installing FM-200 systems across Indonesia’s banking, telecommunications, industrial, and commercial sectors.

Where Is FM-200 Used?

Server Rooms & Data Centers

FM-200 is the global standard for server room and data center fire protection. The combination of 10-second suppression, zero residue, electrical non-conductivity, and safe-for-occupancy design concentration makes it uniquely suited to protecting live IT infrastructure. PT Totalfire Indonesia has installed FM-200 systems in data centers, bank server rooms, telecommunications NOC facilities, and enterprise IT rooms across Jakarta and throughout Indonesia.

Control Rooms & SCADA Facilities

Process control rooms in power plants, oil & gas facilities, manufacturing plants, and utility infrastructure contain HMI workstations, PLCs, and critical control systems that cannot be exposed to water or conventional suppression agents. FM-200 provides reliable, residue-free protection that preserves control room operability immediately after a fire event.

UPS Rooms & Electrical Switchgear

Uninterruptible power supply (UPS) rooms, main distribution boards (MDB), electrical switchgear rooms, and transformer control rooms are high-value electrical assets requiring suppression that can operate safely in energized electrical environments. FM-200’s electrical non-conductivity and fast suppression make it the specified solution for these critical infrastructure spaces.

Telecommunications Facilities

BTS (Base Transceiver Station) equipment rooms, telecom exchange buildings, network operations centers, and cable head-end rooms house telecommunications infrastructure whose failure would affect large numbers of users. FM-200 provides automatic, 24-hour protection without requiring personnel intervention.

 

Laboratories & Research Facilities

Analytical laboratories, pharmaceutical research facilities, and scientific instrument rooms containing sensitive equipment that would be destroyed by water suppression are protected by FM-200 — ensuring research continuity and protecting expensive instruments from both fire and suppression-related secondary damage.

Electronic Data Processing (EDP) Areas

General EDP areas, computer rooms, and IT infrastructure supporting commercial and industrial operations are standard FM-200 applications. The system can be sized for rooms from small server cabinets to large-scale computing environments.

Archives, Vaults & Document Storage

Physical document archives, financial record vaults, and sensitive media storage rooms require residue-free suppression. FM-200’s zero-residue discharge protects both the documents and the storage facility without post-incident cleanup costs.

Switch & Distribution Cabinets

Individual electrical cabinets, distribution boards, and switchgear enclosures can be protected by compact FM-200 systems — either as standalone cabinet-level protection or as part of a larger room-level system, depending on the risk assessment.

FM-200 System Components

  • FM-200 Cylinder Assembly — Steel cylinders containing liquefied FM-200 pressurized with nitrogen; sized to provide the design agent quantity for the protected volume. Available in a range of cylinder sizes from small (typically 10 kg) to large (147 kg) configurations
  • Cylinder Valve & Solenoid Actuator — The solenoid actuator opens the cylinder valve automatically upon signal from the control panel; a mechanical pull pin provides manual backup activation if electrical power is lost
  • Distribution Piping & Nozzles — Engineered piping network delivering FM-200 from the cylinder(s) to precision-orificed discharge nozzles; nozzle placement calculated to achieve uniform agent distribution throughout the protected volume within the 10-second discharge time
  • FM-200 Control Panel — The system brain; receives signals from fire detectors, manages the pre-discharge sequence (single-zone pre-alarm → cross-zone suppression → time delay countdown → discharge), provides abort functionality, and maintains system in automatic standby. Dual dry-cell battery backup maintains panel operation during power failure
  • Cross-Zoned Smoke Detectors — Photoelectric or ionization smoke detectors in a cross-zone configuration; a single detector activating triggers pre-alarm only — two detectors in separate zones must activate to initiate the suppression sequence, preventing false discharges
  • Pre-Discharge Warning Devices — Multi-tone sounders (minimum 94 dB) inside the protected space and at all access doors, providing mandatory evacuation warning; visual strobes for hearing-impaired personnel
  • Gas Discharge Indicator Lamps — Visual indicators above all access doors that illuminate when FM-200 discharge is initiated, warning personnel not to enter the space
  • Abort Station — Wall-mounted manual override at each egress point allowing authorized personnel to halt the discharge countdown during the pre-discharge delay; must be actively held to prevent discharge
  • Manual Release Station — Allows manual system activation in emergency conditions where automatic detection has failed; for use by trained personnel only
  • Pressure Switch & Low-Agent Alarm — Monitors cylinder pressure continuously; alerts maintenance personnel if agent quantity falls below minimum due to leakage between inspections
  • Door Releases & HVAC Shutdown Interface — Automatic fire door closers and HVAC damper releases activated on alarm to seal the protected enclosure and prevent FM-200 loss through air handling openings

How an FM-200 System Works — Step by Step

  1. Single Zone Detection (Pre-Alarm) — A smoke detector in the first zone activates. The FM-200 control panel triggers a pre-alarm: multi-tone sounders inside the protected space activate, warning all personnel to evacuate. No suppression action occurs at this stage
  2. Cross-Zone Detection (Suppression Sequence Initiated) — A second smoke detector in the cross-zone activates, confirming a genuine fire event. The control panel begins the suppression sequence
  3. Pre-Discharge Time Delay — A programmable countdown (typically 30 seconds per NFPA 2001 requirements) provides time for complete evacuation. Gas discharge indicator lamps illuminate above all doors. The abort station can halt the sequence if needed
  4. HVAC Shutdown & Door Closure — HVAC systems supplying the protected space are de-energized and fire-rated dampers close automatically, sealing the room to retain FM-200 at design concentration
  5. Solenoid Valve Opens — The solenoid actuator on the FM-200 cylinder valve opens, releasing liquefied FM-200 under nitrogen pressure into the distribution piping
  6. Agent Discharge & Vaporization — FM-200 flows through the piping and discharges through the nozzles as a rapidly vaporizing gas, flooding the entire protected volume uniformly within 10 seconds
  7. Fire Suppression — FM-200 simultaneously absorbs heat and interrupts combustion chemistry, collapsing the fire before it can grow. The oxygen level in the room remains at safe levels for personnel — a critical distinction from CO2 systems
  8. Hold Period — Per NFPA 2001, a minimum of 85% of the design FM-200 concentration must be maintained for at least 10 minutes after discharge to ensure complete fire suppression and prevent re-ignition. This requires adequate enclosure integrity
  9. Post-Discharge Ventilation — After the fire is confirmed extinguished by qualified personnel, the space is ventilated to remove FM-200 and any combustion products before full re-entry
  10. System Reset & Recharge — Discharged cylinders are identified and sent for recharging. The system is reset to automatic standby and the protection enclosure is restored

FM-200 vs. Other Gaseous Suppression Agents

Feature FM-200 (HFC227ea) Novec 1230 Inert Gas (IG-541) CO₂
Discharge time ✅ ≤10 seconds ✅ ≤10 seconds ~60 seconds ~60 seconds
Safe for occupied spaces ✅ Yes (NOAEL: 9%) ✅ Yes (NOAEL: 10%) ✅ Yes (within design limits) ❌ No — hazardous at design concentration
Leaves residue None None None None
Electrically non-conductive ✅ Yes ✅ Yes ✅ Yes ✅ Yes
Design concentration 7–8% 5.3–5.6% ~40–43% ~34%
Storage footprint ✅ Compact (liquid) ✅ Compact (liquid) ❌ Larger (high-pressure gas) ✅ Compact (liquid)
Global warming potential ❌ 3,220 ✅ <1 ✅ Zero 1 (reference)
Ozone depletion potential ✅ Zero ✅ Zero ✅ Zero ✅ Zero
Availability (Indonesia) ✅ Readily available ⚠️ Limited (import) ✅ High ✅ Widely available
Track record ✅ 100,000+ systems globally Growing adoption Established ✅ Decades of use
Best suited for Data centers, server rooms (speed priority) Same + eco priority Archives, museums (zero GWP) Unoccupied industrial hazards
Governing standard NFPA 2001 NFPA 2001 / ISO 14520-5 NFPA 2001 / ISO 14520 NFPA 12

For applications where environmental performance is the primary priority alongside fast suppression, see our Novec 1230 System. For unoccupied industrial hazards, see our CO2 System. For zero-GWP requirements, see our Inert Gas System.

Enclosure Integrity — Why It Matters for FM-200

NFPA 2001 requires that a minimum of 85% of the design FM-200 concentration be maintained for at least 10 minutes after discharge. If the protected enclosure has excessive leakage through cable penetrations, raised floor gaps, unsealed HVAC connections, or door gaps, FM-200 will escape and oxygen will re-enter — potentially allowing a fire to re-ignite before suppression is complete.

PT Totalfire Indonesia performs mandatory door fan enclosure integrity testing (per ISO 14520 / NFPA 2001 Annex B) during commissioning of every FM-200 system. The test uses a calibrated fan to measure the enclosure’s leakage area and calculate the predicted agent retention time. All identified leaks are sealed before the system is certified. This step is non-negotiable and is a standard part of our commissioning scope — not an optional add-on.

Our FM-200 System EPC Process

  1. Site Survey & Risk Assessment — We survey the protected space: dimensions, ceiling height, raised floor depth, false ceiling void, cable penetrations, HVAC connections, door sealing quality, and existing detection infrastructure
  2. Agent Quantity Calculation — Full NFPA 2001-compliant calculation of FM-200 quantity based on net protected volume (accounting for raised floor and false ceiling voids), design concentration (7–8% for Class A/B/C hazards), temperature correction, and altitude factors for the specific installation location in Indonesia
  3. Cylinder & Piping Design — Cylinder quantity and size selection, piping network layout, nozzle selection and placement, hydraulic pressure calculations to verify uniform distribution within 10-second discharge time
  4. Detection System Design — Cross-zoned smoke detector layout, control panel specification, and integration with the building fire alarm system, access control, and HVAC controls
  5. Equipment Procurement — FM-200 cylinders pre-filled with agent, solenoid valves, distribution piping, nozzles, control panel, smoke detectors, sounders, strobes, abort stations, and door releases sourced from certified manufacturers
  6. Installation — Cylinder bracket and rack installation, piping fabrication and installation, nozzle mounting, control panel installation and wiring, smoke detector installation, sounder and strobe installation, abort station wiring, HVAC damper and door release interface
  7. Commissioning & Integrity Test — Full system functional test: cross-zone activation simulation, time delay verification, abort station test, HVAC shutdown and door release confirmation — followed by door fan enclosure integrity test per NFPA 2001 Annex B / ISO 14520
  8. Personnel Training — Training for facility personnel on system operation, pre-discharge alarm signals, evacuation procedure, abort station use, and post-discharge re-entry protocol
  9. Annual Maintenance — Cylinder weight verification (agent quantity check), solenoid and actuator inspection, smoke detector functional test, control panel battery test, nozzle inspection, and enclosure integrity re-test as required per NFPA 2001

For post-commissioning care, visit our Service & Maintenance page.

FM200 Fire Suppression System di Ruang Server dan data center

Other Gaseous Fire Suppression Systems We Install

  • Novec 1230 System — Next-generation clean agent with near-zero GWP; same 10-second suppression speed as FM-200 with superior environmental credentials
  • Inert Gas System — Zero GWP naturally occurring gas blend for archives, museums, and facilities with strict environmental requirements
  • CO2 System — Cost-effective total flooding and local application for unoccupied industrial hazards and machinery

Related Fire Protection Systems

  • Sprinkler System — Automatic water-based suppression for the broader facility surrounding the FM-200-protected room
  • Wet Pipe System — For offices, corridors, and common areas adjacent to the server room
  • Fire Hydrant System — Manual large-scale suppression for the overall facility
  • Water Spray System — For transformer and industrial equipment protection in the same facility

Frequently Asked Questions — FM-200 Fire Suppression Systems

Why is FM-200 the most popular clean agent for server rooms in Indonesia?

FM-200 dominates the server room and data center market for four compounding reasons: it suppresses fire in 10 seconds or less before significant equipment damage occurs; it leaves zero residue so servers need no cleanup or decontamination; it is electrically non-conductive so it can discharge safely into live electrical environments; and it is safe for brief human occupancy at design concentration unlike CO2. Add to this its compact storage footprint, its proven 100,000+ installation track record globally, and the ready availability of FM-200 agent recharging in Indonesia — and no other suppression option matches its combination of performance, practicality, and proven reliability for this specific application.

What is the difference between FM-200 and Novec 1230?

Both FM-200 and Novec 1230 are clean agents that suppress fire in 10 seconds or less, leave zero residue, and are safe for occupied spaces. The primary distinction is environmental performance: Novec 1230 has a global warming potential (GWP) of less than 1, compared to FM-200’s GWP of 3,220 — making Novec 1230 significantly more environmentally sustainable and better positioned for long-term regulatory compliance as HFC phase-down policies evolve globally. For organizations without specific sustainability mandates, FM-200 remains the more established choice with a larger installed base and slightly wider agent availability in Indonesia. For organizations with environmental commitments, Novec 1230 is the preferred alternative. Learn more about our Novec 1230 systems.

Is FM-200 safe if someone is in the room when it discharges?

FM-200 at its design concentration of 7–8% by volume is within the NOAEL (No Observed Adverse Effect Level) safety limit established by NFPA 2001 — meaning no adverse physiological effects are expected at this concentration for the brief period of exposure during and immediately after discharge. This is a significant safety advantage over CO2, which at suppression concentrations is immediately dangerous to human life. However, evacuation is always mandatory before or immediately upon any FM-200 discharge — the NOAEL limit is a safety margin, not a green light to remain in the space during or after suppression. The pre-discharge alarm and time delay sequence is specifically designed to ensure complete evacuation before agent release.

How much space does an FM-200 system require for cylinder storage?

FM-200 is stored as a liquefied gas and is highly efficient in terms of storage density. For a typical 50 m² server room at standard ceiling height, a complete FM-200 system might require between two and six cylinders, occupying approximately 0.5–1.5 m² of floor space. Cylinders can be located inside the protected room itself or in an adjacent equipment corridor or dedicated suppression room. PT Totalfire Indonesia provides cylinder storage layout options as part of the system design to minimize the impact on usable floor space in your facility.

Can one FM-200 system protect multiple rooms?

Yes. Multi-zone FM-200 systems use selector valves to direct agent from a shared cylinder bank to the specific protected room where fire has been detected. This is common in facilities with multiple server rooms, UPS rooms, and control rooms — allowing a single master cylinder bank to cover several independent zones while reducing total installed agent quantity and cylinder count compared to individual single-zone systems. PT Totalfire Indonesia designs multi-zone selector valve systems as part of our standard engineering scope. Each zone has its own independent detection system and pre-discharge sequence.

How often does an FM-200 system need maintenance?

Per NFPA 2001, FM-200 systems require annual inspection including: cylinder weight verification (to confirm agent quantity — cylinders with more than 5% agent loss must be recharged), valve and solenoid actuator inspection, smoke detector functional test, control panel battery replacement or test, nozzle visual inspection for blockage or damage, and enclosure integrity assessment. A full door fan integrity test should be repeated every two to three years or after any significant penetration work in the protected enclosure. PT Totalfire Indonesia provides annual maintenance contracts covering all required NFPA 2001 inspection and testing activities. Contact us to discuss a maintenance agreement.

Can FM-200 be installed in a raised floor data center?

Yes, and this is one of the most technically important design considerations for FM-200 data center installations. Data centers with raised floors have two distinct volumes — the room above the floor and the plenum beneath it — and the fire suppression system must protect both. PT Totalfire Indonesia designs FM-200 systems for raised floor environments using a combination of above-floor and below-floor nozzles, with agent quantity calculated for the total combined volume including both the main room and the raised floor plenum. Raised floor and false ceiling integrity are also specifically addressed during the enclosure integrity test.

PT. Totalfire Indonesia

PT. Totalfire Indonesia, established in May 2005, is a trusted fire protection system contractor in Jakarta, Indonesia. As a fire protection specialist with ISO 45001 and ISO 9001 certification, we provide engineering, installation, and maintenance services for fire protection systems across commercial and industrial projects, ensuring compliance with NFPA and SNI standards.

Market Range

Industrial Building
Power Plant
Mining Company
Oil and Gas Company
Telecommunication Company
Commercial Building
Residential Building

Contact Us

Ruko Prominence Alam Sutera, Blok 38E No.49

Jl Jalur Sutera, Panunggangan Timur, Pinang

Tangerang Selatan, Banten - Indonesia 15325

Telephone : (+6221) 300 525 33
FAX : (+6221) 300 525 32
E-mail : info@totalfire.co.id