Gaseous Fire Suppression System
Carbon Dioxide(CO2)
Fire Suppression System
Category: Gaseous Fire Suppression System
Carbon Dioxide (CO2) Fire Suppression System — Industrial Fire Protection in Indonesia
PT Totalfire Indonesia designs and installs Carbon Dioxide (CO2) fire suppression systems for industrial machinery, power generation equipment, cable infrastructure, process plant hazards, and other high-risk applications across Indonesia. CO2 is one of the oldest, most proven, and most cost-effective gaseous suppression agents available — and remains the preferred choice for protecting unoccupied industrial hazards where its unique combination of deep flooding, residue-free discharge, and compact storage is unmatched.
All our CO2 system designs comply with NFPA 12 (Standard on Carbon Dioxide Extinguishing Systems) and SNI national fire safety standards, backed by our ISO 9001:2015 and ISO 45001:2018 certifications.
What Is a CO2 Fire Suppression System?
A Carbon Dioxide (CO2) fire suppression system is a fixed automatic gaseous suppression system that discharges CO2 — a naturally occurring, electrically non-conductive, residue-free gas — into a protected enclosure or directly onto a localized hazard to extinguish fire rapidly and completely.
CO2 extinguishes fire through two simultaneous mechanisms:
- Oxygen displacement — CO2 is 1.5 times heavier than air. When discharged, it rapidly displaces oxygen in the protected space, reducing the oxygen concentration below the level required to sustain combustion (typically below 15% for most flammable materials, compared to 20.9% in normal air)
- Heat absorption — CO2 discharges at very low temperatures and absorbs significant heat energy from the fire as it vaporizes, actively cooling the combustion zone
Because CO2 is a natural component of the atmosphere and leaves absolutely no residue after discharge, protected equipment and surfaces require no cleanup or decontamination after system activation — a significant operational and cost advantage over powder-based or foam suppression alternatives.
Critical safety note: CO2 at fire-suppression concentrations is hazardous and potentially fatal to humans. CO2 systems are designed for areas that are normally unoccupied, or where positive confirmation of evacuation before discharge can be reliably achieved. For areas with regular human occupancy, clean agent systems such as FM-200 or Novec 1230 are the appropriate alternative.
CO2 System Application Methods
Total Flooding
In total flooding applications, CO2 is discharged into a fully enclosed space — a room, cabinet, or sealed enclosure — flooding the entire volume to achieve and maintain a uniform suppression concentration throughout. Total flooding is used when the hazard occupies or could spread to fill the entire protected space.
Design concentration: Typically 34% CO2 by volume for Class B and C hazards in total flooding applications, or higher for specific materials. The system must maintain this concentration for the required hold time (per NFPA 12, a minimum 20-minute soak period for surface fires) to prevent re-ignition.
Typical total flooding applications:
- Electrical switchgear rooms and cable spreading rooms
- Diesel generator rooms
- Transformer vaults
- Ship engine rooms and machinery spaces
- Printing machinery enclosures
- Dust collector and filter housings
- Silos and process enclosures
Local Application
In local application, CO2 nozzles are positioned to discharge directly onto a specific piece of equipment or a defined surface hazard — without requiring the surrounding area to be enclosed. The agent is applied at a high rate directly to the flame front and the surface from which fire is being generated.
Design approach: Nozzles are engineered to achieve the required application rate over the full surface area of the hazard within the specified discharge time, maintaining agent concentration at the surface despite the absence of enclosure containment.
Typical local application uses:
- Aluminum rolling mills and metal processing equipment
- Hydraulic systems and oil-lubricated machinery
- Dip tanks and quench tanks
- Paint and powder coating booths
- Printing press ink systems
- Conveyor belts and dryers
- Open turbine enclosures and bearing assemblies
Where Is a CO2 System the Right Choice?
CO2 is the preferred suppression agent when all of the following conditions apply:
- The protected area is normally unoccupied — or evacuation before discharge can be positively confirmed through detection and pre-discharge warning sequences
- The hazard involves Class B (flammable liquids) or Class C (electrical) fires, or certain Class A deep-seated hazards where extended soak time is required
- The facility requires a residue-free suppression agent that does not contaminate equipment or surrounding surfaces
- The application requires compact agent storage — CO2 is stored as a liquefied gas under pressure and requires significantly less storage space than equivalent inert gas systems
- Cost efficiency is a priority — CO2 is generally the most economical gaseous suppression agent on a per-unit-volume basis, and CO2 cylinders can be refilled locally in Indonesia
Typical Applications of CO2 Fire Suppression Systems
| Industry / Facility | Protected Asset / Area | Method |
|---|---|---|
| Power Generation | Turbines, transformer vaults, cable spreading rooms | Total flooding / Local application |
| Oil & Gas | Compressor enclosures, pump stations, machinery spaces | Total flooding / Local application |
| Industrial Manufacturing | Rolling mills, hydraulic systems, machine tools | Local application |
| Paint & Coating Plants | Spray booths, powder coating booths, varnishing lines | Local application |
| Printing Industry | Print machinery, ink systems, dryer units | Local application / Total flooding |
| Marine & Shipping | Ship engine rooms, pump rooms, cargo holds | Total flooding |
| Industrial Storage | Silos, dust collectors, filter housings, hazardous material stores | Total flooding |
| Electrical Infrastructure | Switchgear rooms, cable trays and shafts, control systems | Total flooding |
| Testing & R&D Facilities | Motor testbeds, engine test cells, dynamometer rooms | Total flooding |
| Metal Processing | Quench tanks, dip tanks, special metal processing plants | Local application |
CO2 vs. Other Gaseous Suppression Agents
| Feature | CO2 | FM-200 (HFC227ea) | Novec 1230 | Inert Gas (IG-541) |
|---|---|---|---|---|
| Safe for occupied spaces | ❌ No — toxic at design conc. | ✅ Yes | ✅ Yes | ⚠️ Evacuation required |
| Activation time | ~60 seconds | ≤10 seconds | ≤10 seconds | ~60 seconds |
| Residue after discharge | None | None | None | None |
| Storage footprint | ✅ Compact | ✅ Compact | ✅ Compact | ❌ Larger (high-pressure cylinders) |
| Agent refill availability in Indonesia | ✅ Widely available | ✅ Available | ⚠️ Limited | ✅ Available |
| Installation cost | ✅ Lowest | Moderate | Higher | Moderate–High |
| Global warming potential (GWP) | 1 (reference) | 3,220 | <1 | Zero |
| Best suited for | Unoccupied industrial, machinery, process hazards | Server rooms, data centers, occupied spaces | Occupied spaces, environmental priority | Archives, museums, zero-GWP requirement |
| Governing standard | NFPA 12 | NFPA 2001 | NFPA 2001 / ISO 14520-5 | NFPA 2001 / ISO 14520 |
Key Components of a CO2 Fire Suppression System
- CO2 Storage Cylinders — High-pressure cylinders containing liquefied CO2 under pressure, sized to provide the design quantity required for the protected hazard. Available in standard 45 kg cylinders; multiple cylinders manifolded together for larger systems
- Cylinder Valve & Solenoid Actuator — Controls agent release; the solenoid actuator opens the cylinder valve automatically upon signal from the control panel, or manually via the mechanical pull station
- Distribution Piping & Nozzles — Engineered pipe network delivering CO2 from the cylinder bank to the discharge nozzles at the calculated flow rate and pressure; nozzle type and placement determined by application method (total flooding or local application)
- CO2 Control Panel — The system brain; receives signals from fire detectors, manages the pre-discharge sequence (alarm, time delay, abort function), and triggers agent release. Provides automatic and manual operation modes
- Fire Detection Devices — Smoke detectors, heat detectors, or flame detectors (cross-zoned for reliability) monitoring the protected space continuously
- Pre-Discharge Warning Devices — Audible alarms (alarm bells or multi-tone sounders at 94 dB+) and visual indicators (strobe lights, gas discharge indicator lamps) providing mandatory warning before agent release
- Manual Pull Station — Allows manual system activation in the event of detector failure or for emergency use by trained personnel
- Abort Station — Allows authorized personnel to halt the discharge sequence during the pre-discharge countdown if the alarm is false; critical safety device in areas with any personnel access
- Pressure Switch & Low-Pressure Alarm — Monitors cylinder pressure continuously; alerts maintenance team if agent quantity falls below minimum level due to leakage
- Door Releases & HVAC Shutdown — Automatically closes fire doors and shuts down HVAC systems serving the protected space on alarm activation, preventing agent loss through air handling openings
How a CO2 Fire Suppression System Works
- Detection — Single Zone (Pre-Alarm) — The first fire detector activating triggers a pre-alarm: audible alarms sound inside the protected space, warning any personnel to evacuate immediately
- Detection — Cross-Zone (Suppression Sequence) — A second detector in the cross-zone activates, confirming a genuine fire event and initiating the suppression sequence
- Pre-Discharge Countdown — The control panel begins a programmable time delay (typically 30 seconds) allowing complete evacuation. Visual gas discharge indicator lamps illuminate. The abort station can halt the sequence if needed
- HVAC Shutdown & Door Closure — HVAC systems are de-energized and fire-rated dampers close automatically, sealing the protected space to prevent CO2 loss
- Agent Discharge — The solenoid actuator opens the cylinder valve(s). CO2 flows through the distribution piping and discharges through the nozzles into the protected space at high velocity
- Suppression — CO2 rapidly fills the space, displacing oxygen and absorbing heat. Fire suppression occurs as the oxygen concentration drops below the combustion threshold — typically within 60 seconds of discharge initiation
- Hold Period (Soak Time) — Per NFPA 12, the CO2 concentration must be maintained for the required soak time — a minimum of 20 minutes for surface fires and longer for deep-seated fires — to ensure complete extinguishment and prevent re-ignition
- Post-Discharge Ventilation — After fire suppression is confirmed by qualified personnel, the space is ventilated to remove CO2 before re-entry. The system is inspected, cylinders are recharged, and the system is reset to automatic standby
Important Safety Requirements for CO2 Systems
Because CO2 at suppression concentrations is immediately dangerous to life and health (IDLH: 40,000 ppm / 4%), CO2 systems carry specific mandatory safety requirements that PT Totalfire Indonesia implements as standard on every installation:
- Pre-discharge warning devices — Audible and visual alarms must activate before agent discharge with sufficient time for complete evacuation of the protected space
- Time delay — A minimum programmable pre-discharge delay must be provided to allow evacuation
- Abort station — A manually operated device to halt the discharge sequence must be provided at each egress point from the protected area
- Warning signs — Permanent hazard warning signs in Bahasa Indonesia and English must be posted at all access points to CO2-protected areas
- Personnel training — All facility personnel who may access CO2-protected areas must be trained on system operation, warning signals, evacuation procedures, and re-entry protocols
- Lock-out/tag-out procedure — Cylinder isolation valves must be in the locked-open or locked-closed position as required during maintenance, with clear administrative procedures governing system isolation
Our CO2 System EPC Process
- Hazard Assessment — We classify the protected hazard (Class B, C, or A deep-seated), determine the application method (total flooding or local application), and assess enclosure integrity for total flooding applications
- CO2 Quantity Calculation — Full NFPA 12-compliant agent quantity calculation based on enclosure volume, design concentration, temperature correction factors, and leakage compensation
- System Design — Cylinder bank sizing, piping network design, nozzle selection and placement, control panel specification, detection layout, and safety device placement
- Equipment Procurement — CO2 cylinders, valves, actuators, distribution piping, nozzles, control panel, detection devices, alarm devices, abort stations, and door releases from certified manufacturers
- Installation — Cylinder rack installation, piping and nozzle installation, control panel wiring, detection device installation, HVAC shutdown interface, door release installation, and safety signage
- Commissioning & Functional Testing — Full system functional test including detector activation, pre-discharge sequence verification, abort function test, HVAC shutdown confirmation, and door closure test — all without discharging CO2 agent
- Personnel Training — Training for facility personnel on system operation, warning signal recognition, evacuation procedures, abort station use, and post-discharge re-entry protocols
- Ongoing Maintenance — Annual inspection per NFPA 12 including cylinder weight verification, valve and actuator inspection, detector testing, piping and nozzle inspection, and low-pressure alarm test
For post-commissioning system care, visit our Service & Maintenance page.
Other Gaseous Fire Suppression Systems We Install
CO2 is one of four gaseous suppression agents offered by PT Totalfire Indonesia. For occupied spaces or applications with different requirements, explore our other options:
-
- FM-200 (HFC227ea) System — Fast-acting clean agent safe for occupied spaces; the standard choice for server rooms, data centers, and control rooms
- Novec 1230 System — Next-generation clean agent with near-zero GWP; safe for occupied spaces and the most environmentally sustainable option
- Inert Gas System — Naturally occurring gas blend with zero GWP; safe for brief human exposure and ideal for archives, museums, and heritage facilities
Related Fire Protection Systems
- Sprinkler System — Automatic water-based suppression for the broader facility surrounding CO2-protected enclosures
- Water Spray System — Fixed directional water spray for transformer cooling and industrial equipment protection
- Fire Hydrant System — Manual large-scale suppression for the overall facility
- Foam System — For flammable liquid hazards outside CO2-protected enclosures
Frequently Asked Questions — CO2 Fire Suppression Systems
Why is CO2 dangerous to humans at fire-suppression concentrations?
Normal air contains approximately 0.04% CO2. At concentrations above 4% (40,000 ppm), CO2 causes immediate symptoms including headache, dizziness, and loss of consciousness. Fire suppression concentrations for CO2 systems are typically 34% or higher — more than 800 times the normal atmospheric level — which is immediately dangerous to life and health (IDLH) and can cause rapid unconsciousness and death without warning. This is why CO2 systems are restricted to normally unoccupied areas and require mandatory pre-discharge warning, time delay, and evacuation confirmation before discharge.
What is the difference between total flooding and local application CO2 systems?
Total flooding discharges CO2 into a completely enclosed space — flooding the entire room volume to achieve design concentration throughout. It requires the enclosure to be sufficiently airtight to retain agent for the soak period. Local application discharges CO2 directly onto a specific piece of equipment or surface hazard at a high application rate, without requiring an enclosure. Local application is used where enclosure is not practical — such as open industrial machinery, rolling mills, and outdoor process equipment. PT Totalfire Indonesia designs both types per NFPA 12.
Can CO2 be used to protect server rooms or data centers?
CO2 can technically suppress fires in server rooms, but it is not recommended for occupied or regularly accessed spaces such as data centers. At suppression concentrations, CO2 is immediately life-threatening. Modern data centers and server rooms should use FM-200 or Novec 1230 — clean agents that suppress fire at concentrations safe for brief human exposure. CO2 is best reserved for unoccupied industrial applications where its cost and agent availability advantages can be realized safely.
How long must CO2 concentration be maintained after discharge?
Per NFPA 12, the design concentration must be maintained for the full soak period — a minimum of 20 minutes for surface fire hazards (flammable liquids), and longer for deep-seated fires (smoldering combustibles like cotton, paper in bales, or electrical cable insulation). The soak period allows heat to dissipate from the protected material below the re-ignition temperature. This requirement drives the agent quantity calculation and the enclosure integrity requirements for total flooding systems.
How often does a CO2 system need to be inspected and maintained?
Per NFPA 12 and NFPA 25, CO2 systems require: monthly visual inspection of cylinders and gauges, annual inspection including cylinder weight verification (to detect leakage), functional test of detection devices and pre-discharge sequence, valve and actuator inspection, nozzle condition check, and piping integrity assessment. Cylinders that have lost more than 5% of their original agent weight must be recharged or replaced. PT Totalfire Indonesia provides scheduled maintenance contracts covering all required annual inspection and testing activities. Contact us to discuss a maintenance agreement.
Can CO2 cylinders be refilled locally in Indonesia?
Yes — CO2 is widely available in Indonesia and cylinders can be refilled locally after discharge, making CO2 one of the most practical gaseous suppression agents for facilities in Indonesia from a supply chain and long-term operational perspective. This is one of the key cost advantages of CO2 over specialty clean agents such as Novec 1230, which may require importation for recharge.
PT. Totalfire Indonesia
PT. Totalfire Indonesia, established in May 2005, is a trusted fire protection system contractor in Jakarta, Indonesia. As a fire protection specialist with ISO 45001 and ISO 9001 certification, we provide engineering, installation, and maintenance services for fire protection systems across commercial and industrial projects, ensuring compliance with NFPA and SNI standards.
Market Range
Industrial Building
Power Plant
Mining Company
Oil and Gas Company
Telecommunication Company
Commercial Building
Residential Building
Contact Us
Ruko Prominence Alam Sutera, Blok 38E No.49
Jl Jalur Sutera, Panunggangan Timur, Pinang
Tangerang Selatan, Banten - Indonesia 15325